You are here:

AI880A 3BSE039293R1 | CI860K01 3BSE032444R1 | Integrity simulation input module

Product model: AI880A

Item number: 3BSE039293R1

Category Description: Integrity simulation input module

Product color: new, not new

Warranty: One year

Stock: Yes

Brand: ABB

Categories:
Email:jllucky33@qq.com
phone:(86)17372046300

Product content

AI880A 3BSE039293R1 | CI860K01 3BSE032444R1 | Integrity simulation input module

Product model: AI880A

Item number: 3BSE039293R1

Category Description: Integrity simulation input module

Product color: new, not new

Warranty: One year

Stock: Yes

Brand: ABB

dimension

Width 45 mm (1.77 in)

Depth 102 mm (4.01 “), 111 mm (4.37 “) including connector

Height 119 mm (4.7 in)

Weight 0.15 kg (0.33 lb)

Detailed data

Resolution 12 bits

Input impedance 250Ω with shunt rod TY801 (current input)

Isolation groups are isolated from the ground

Below/Out range Overrange: +12% (0… 20 mA), +15% (4… 20 mA)

Error maximum 0.1%

Maximum temperature drift of 50 ppm/°C

 

 

Input filter (rise time 0-90%) 190 ms (hardware filter)

The update cycle time is 10 milliseconds

Current limit Built-in current limits transmitter power

Maximum field cable length 600 meters (656 yards)

Maximum input voltage (non-destructive) 11 V DC

NMR, 50 Hz, 60 Hz > 40 dB

Rated insulation voltage 50 volts

The AI880A High integrity analog input module is designed for single and redundant configurations. The module has 8 current input channels. The input resistance is 250 ohms.

This module allocates external transmitter power to each channel. This adds a simple connection that distributes power to a 2 – or 3-wire transmitter. Transmitter power is monitored and current limited. All eight channels are isolated from the ModuleBus in a group. The power supply for the module is generated by 24 V on the ModuleBus.

The AI880A complies with NAMUR Recommendation NE43 and supports configurable overrange and underrange limits.

Characteristics and advantages

8 channels for 0… 20 mA, 4… 20 mA, single-ended unipolar input

Single or redundant configuration

1 group of 8 channels, isolated from the ground

12-bit resolution

Loop monitors the DI function

Configurable field power output alarm limits

Configurable over/under range of current input

Each channel current limits the transmitter power supply

Advanced on-board diagnostics

SIL3 certified by IEC 61508

Category 4 certification according to EN 954-1

Complies with NAMUR recommendation NE43 and supports configurable overrange and underrange limits

HART Direct Communication (AI880A)