AI893 3BSC690141R1 | Analog input module | AI930N 3KDE175513L9300
Product model: AI893
Item number: 3BSC690141R1
Category Description: Analog input module
Product color: new, not new
Warranty: One year
Stock: Yes
Brand: ABB
Categories: ABB
Tags: AI893 3BSC690141R1
Email:jllucky33@qq.com
phone:(86)17372046300
Product content
AI893 3BSC690141R1 | Analog input module | AI930N 3KDE175513L9300
Product model: AI893
Item number: 3BSC690141R1
Category Description: Analog input module
Product color: new, not new
Warranty: One year
Stock: Yes
Brand: ABB
dimension
Width 45 mm (1.77 in)
Depth 102 mm (4.01 “), 111 mm (4.37 “) including connector
Height 119 mm (4.7 in)
Weight 0.16 kg (0.35 lb)
Detailed data
Resolution 15 bit + symbol
Input impedance >10 MΩ
Isolation groups are isolated from the ground
Error TC/mV: <20 μV; RTD (0-400 Ω) : < 0.1Ω; RTD (0-4000 Ω) : <1 Ω
Temperature drift thermocouple/millivolt: <20 μV/10°C; Thermal resistance (0-400Ω) : < 0.1Ω /10°C; RTD (0-4000 Ω) : <1 Ω/10°C
Update cycle time (number of active channels) x 125 + 125 ms
Common-mode voltage input +/- 5V
Common mode rejection ratio (CMRR), 50Hz, 60Hz >100 dB
NMR, 50 Hz, 60 Hz >80 dB
Rated insulation voltage 50 volts
The AI893 analog input module has 8 channels. The module contains intrinsically safe protection components on each channel for connecting process equipment to hazardous areas without the need for additional external equipment.
The module can be configured as a 2-wire or 3-wire RTD sensor or TC sensor. In TC mode, channel 8 is used for cold end (ambient) temperature measurement and thus used as channel 1. CJ channel of 7. The junction temperature can be measured either locally on the MTU screw terminal or on a connection unit far from the device. The cold end temperature is measured using a 3-wire Pt 100 sensor. Alternatively, the user can set the fixed junction temperature of the module (as a parameter). When CJ temperature measurements are not required, channels 8 can be used in the same way as channels 1-7.
The TU890 and TU891 compact Mtus can be used with this module to enable three-wire connections to process equipment without the need for additional terminals. The TU890 is for explosion-proof applications and the TU891 is for non-explosion-proof applications.
Characteristics and advantages
• 8 differential input channels for 2-wire or 3-wire RTDS and thermocouples.
• 1 group of 8 channels isolated from the ground.
• 15 bit + symbol resolution.
• Explosion-proof certification input.
Reviews