You are here:

AIS815 2PAA123602R1 | Analog input module is connected to field equipment to perform necessary signal conditioning

Model: AIS815

Item number: 2PAA123602R1

Category: Analog input module

Finish: New, not new

Warranty: One year

Brand: ABB

Categories:
Email:jllucky33@qq.com
phone:(86)17372046300

Product content

 

Model: AIS815

Item number: 2PAA123602R1

Category: Analog input module

Finish: New, not new

Warranty: One year

Brand: ABB

dimension

Width 77.9 mm

Depth 105 mm

Height 9.8 mm

Weight (including base) 73g

Signal Specification 4… 20 ma

0… 20 ma

Hart, yes.

Detailed data

Supported field equipment 2 wires (loop powered transmitter) 3 wires (SCM powered transmitter) 4 wires (SCM powered transmitter)

Isolation Electrical isolation from the system. 3060 V DC is used for routine testing in the factory.

Field power current Limit (configurable)

Accuracy 0.1 %

Resolution 16-bit A/D converter

Diagnostic loop monitoring (open and short circuits)

The device fault is low, below range, over range, and high

Internal hardware monitoring

Communication monitoring

Internal power monitoring

Power injection monitoring

Calibration factory calibration

Power consumption 0.63 watts

Install in hazardous areas/locations yes/yes

IS no barrier

Field input robustness ±35 V, between all terminals

Input voltage range 19.2… 30 volt

Input impedance 250 ohms

Detailed HART information HART v7, HART pass-through and HART variables to applications

Select I/O is an Ethernet networked single-channel granular I/O System for the ABB Ability™ System 800xA automation platform. Select I/O helps decoupage project tasks, minimizes the impact of late changes, and supports the standardization of I/O cabinets, ensuring automation projects are delivered on time and on budget. The Signal Conditioning Module (SCM) performs the necessary signal conditioning and power supply for connected field devices in an I/O channel.

The AIS810 is an analog input signal conditioning module (16-bit) that supports 2/4-wire devices and HART communication.

Characteristics and advantages

Analog input for 2-wire or externally powered 4-wire field devices

Signal range: 4… 20 mA and 0… 20 mA

Can be used in dangerous areas

Transmitter power current is limited to 30 mA

16-bit A/D converter resolution

Current isolation between channels

Hardware filter, rise time 1ms

The software filter can be configured by parameters

Prevent miswiring

Configurable software filters

Diagnosis:

Loop monitoring (open and short)

Hardware error monitoring

Communication supervision