You are here:

AI815 3BSE052604R1 | Analog input module

 

Model: AI815

Item number: 3BSE052604R1

Series: S800 series

Category: Analog input module

Finish: New, not new

Warranty: One year

Stock: Yes

Brand: ABB

Categories:
Tags:
Email:jllucky33@qq.com
phone:(86)17372046300

Product content

 

Model: AI815

Item number: 3BSE052604R1

Series: S800 series

Category: Analog input module

Finish: New, not new

Warranty: One year

Stock: Yes

Brand: ABB

dimension

Width 45 mm (1.77 in)

Depth 102 mm (4.01 “), 111 mm (4.37 “) including connector

Height 119 mm (4.7 in)

Weight 0.23 kg (0.51 lb)

Signal specification: 0… 20 mah, 4… 20 mah, 0… 5 volts, 1… 5 Volts

Number of channels: 8

Signal type: Unipolar single-ended

 

The AI815 analog input module has 8 channels. These modules can be configured for voltage or current input. Current and voltage signals cannot be mixed on the same I/O module. Voltage and current inputs can withstand overvoltage or undervoltage of at least 11 V DC.

The input resistance of the voltage input is greater than 10 M ohms and the input resistance of the current input is 250 Ω. The module allocates external HART compatible transmitter power to each channel. This adds a simple connection that distributes power to a 2 – or 3-wire transmitter. Transmitter power is monitored and current limited. If an external power supply is used to power the HART transmitter, the power supply must be compatible with HART.

Characteristics and advantages

8 channels for 0… 20 mA, 4-20 mA, 0-5 V or 1-5 V DC, single-ended unipolar input

1 group of 8 channels, isolated from the ground

12-bit resolution

Each channel current limits the transmitter power supply

HART direct communication

Detailed data

Resolution 12 bits

Input impedance 10 MΩ (voltage input)

250 Ω (current input)

Isolation groups are isolated from the ground

Below/out of range 0 / +15% (0… 20 mA, 0… 5 V), -12.5% / +15% (4… 20 mA, 1… 5 V)

Error maximum 0.1%

Maximum temperature drift of 50 ppm/°C

Input filter (rise time 0-90%) 290 ms

The update cycle time is 10 milliseconds

Current limit Built-in current limits transmitter power

Maximum field cable length 600 meters (656 yards)

NMR, 50 Hz, 60 Hz > 40 dB

Rated insulation voltage 50 volts

Dielectric test voltage 500 V AC

Power consumption 3.5 Watts

Current consumption +5 V Modulebus 100 MA

You may also like

Reviews (no reviews yet)

Reviews

There are no reviews yet.

Be the first to review “AI815 3BSE052604R1 | Analog input module”

Your email address will not be published. Required fields are marked *