You are here:

AI890  3BSC690071R1 | Analog input module AI910N 3KDE175513L9100

Product model: AI890

Item number: 3BSC690071R1

Category Description: Analog input module

Product color: new, not new

Warranty: One year

Stock: Yes

Brand: ABB

Categories:
Email:jllucky33@qq.com
phone:(86)17372046300

Product content

AI890  3BSC690071R1 | Analog input module AI910N 3KDE175513L9100

Product model: AI890

Item number: 3BSC690071R1

Category Description: Analog input module

Product color: new, not new

Warranty: One year

Stock: Yes

Brand: ABB

dimension

Width 45 mm (1.77 in)

Depth 102 mm (4.01 “), 111 mm (4.37 “) including connector

Height 119 mm (4.7 in)

Weight 0.2 kg (0.44 lb)

 

Detailed data

Resolution 12 bits

Quarantine teams are wisely isolated from the ground

Below/out of range 0/22 MA

Error maximum 0.1%

Temperature drift Typical value 50 ppm/°C Maximum value 100 ppm/°C

Input filter (rise time 0-90%) 75 ms

The update cycle time is 5 milliseconds

Current limit Built-in current limits transmitter power

Common mode rejection ratio (CMRR), 50Hz, 60Hz >80 dB

NMR, 50 Hz, 60 Hz >20 dB

Rated insulation voltage 50 volts

Dielectric test voltage 500 V AC

Power consumption 1.5W

Current consumption +5 V Modulebus Typical value 70 mA, maximum 150 mA

Current consumption +24 V External typical value 220 mA, Max <300 mA

The AI890 analog input module has 8 channels. The module contains intrinsically safe protection components on each channel for connecting process equipment to hazardous areas without the need for additional external equipment.

Each channel can be a current input or a power supply and monitor a two-wire process transmitter. Current input A transmitter for external power supply. The input voltage drop for current inputs is typically 3 V (including PTC). Transmitter power supplies in each channel are capable of delivering a minimum of 15 V/20 mA loop current to power Ex certified process transmitters, limited to 23 mA under overload conditions. All 8 channels are isolated from the ModuleBus and power supply in a group. The power of the input stage is converted from 24 V on the power supply connection.

The TU890 and TU891 compact MTU can be used with this module to connect two wires to process equipment without additional terminals. The TU890 is for explosion-proof applications and the TU 891 is for non-explosion-proof applications.

Characteristics and advantages

• 8 channels for 0… 20 mA or 4… 20 mA, single-ended unipolar input.

• 1 group of 8 channels isolated from the ground.

• Power and monitor explosion-proof certified two-wire transmitters.

• Non-energy storage analog input for external power supply.

You may also like

Reviews (no reviews yet)

Reviews

There are no reviews yet.

Be the first to review “AI890  3BSC690071R1 | Analog input module AI910N 3KDE175513L9100”

Your email address will not be published. Required fields are marked *

Post comment