BENTLY 3500/65 145988-02 | Big card | 3500 system expansion module | Channel Temperature Monitor
Description
The 3500/65 145988-02 monitor provides 16 channels of temperature
monitoring and accepts both resistance temperature
detector (RTD) and isolated tip thermocouple (TC)
temperature inputs.
Categories: BENTLY
Tags: 3500/65 145988-02
Email:jllucky33@qq.com
phone:(86)17372046300
Product content
Description
The 3500/65 monitor provides 16 channels of temperature
monitoring and accepts both resistance temperature
detector (RTD) and isolated tip thermocouple (TC)
temperature inputs. The monitor conditions these inputs and
compares them against user-programmable alarm
setpoints.
The monitor is programmed using the 3500 Rack
Configuration Software. You can configure the 16-Channel
Temperature Monitor to accept isolated tip thermocouples,
3-wire RTD, 4-wire RTD, or a combination of TC and RTD inputs.
In Triple Modular Redundant (TMR) configurations, you must
install temperature monitors in groups of 3 adjacent
monitors. In this configuration the monitor uses 2 types of
voting to ensure accurate operation and to avoid single
point failures.
Type E -100°C to +1000°C,
(-148°F to +1832°F)
Type J 0°C to +760 °C
(32°F to +1400 °F)
Type K 0°C to +1370°C
(32°F to +2498°F)
Type T -160°C to +400°C,
( -256°F to +752°F)
Dimensions
(Height xWidth xDepth)
241.3 mm x 24.4 mm x 241.8 mm
(9.50 in x 0.96 in x 9.52 in
FCC
This device complies with part 15 of the
FCC Rules. Operation is subject to the
following two conditions:
l This device may not cause harmful
interference.
l This device must accept any
interference received, including
interference that may cause
undesired operation.
Reviews