Honeywell EG1033AA EG1033AA01 | Flame detector amplifier—Hainian Jinlin
Model: EG1033AA EG1033AA01
Category: Flame detector amplifier
Brand: Honeywell
Warranty: One year
(LG Series)LG series EG amplifier
EG1033AA EG1033AA01
Honeywell gas turbine flame monitoring system
The Honeywell LG/EG Flame monitoring system detects ultraviolet radiation from hydrocarbon flames and produces an output signal to indicate it
Categories: Honeywell
Email:jllucky33@qq.com
phone:(86)17372046300
phone:(86)19389860630
Product content
Model: EG1033AA EG1033AA01
Category: Flame detector amplifier
Brand: Honeywell
Warranty: One year
(LG Series)LG series EG amplifier
EG1033AA EG1033AA01
Honeywell gas turbine flame monitoring system
The Honeywell LG/EG Flame monitoring system detects ultraviolet radiation from hydrocarbon flames and produces an output signal to indicate it
Conditions with or without flame.
The system has delivered proven performance on GE (and GE license-holders) gas turbines for more than 35 years.
Geiger Mueller type sensor photocell.
Detection spectrum 180… Ultraviolet radiation in the 260nm range. Sun-blind, resistant to blackbody radiation.
Two years shelf life, 10,000 hours MTBF, more than 1 billion (109) hours of operation time.
Gas turbines for power generation and compressors
Temperature range: -40… 176C
Hardware output: Only for EG1033 amplifier module
EG1033AA: open transistor collector
EG1033AB and EG1033AC: Relay Contacts (SPDT)
trait
Geiger Mueller type sensor photocell.
Detection spectrum 180… Ultraviolet radiation in the 260nm range.
10,000 hours MTBF with over a billion (109) hours of operation.
Gas turbines for power generation and compressors
Temperature range: -40… 176 degrees Celsius
Hardware output: Only for EG1033 amplifier module
EG1033AA: open transistor collector
EG1033AB and EG1033AC: Relay Contacts (SPDT)
High sensitivity and fast flame presence response time (typical value 0.1 seconds)
Flame loss response time: 0.2 seconds Max
The amplifier supports multiple voltage requirements: 28 Vdc, 20-35 Vdc, and 115 Vac.
Operating distance up to 330 m (1000 ft), sensor to amplifier.
Qualified components on General Electric turbines.
Provides the European Directive CE marking for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Environments 94/9/EC
(EEx d IIA T3 or EEX d IIC T3, Zones 1 and 2).
Factory Mutual certified for explosive environments (Class I, Zones 1 and 2, Groups B, C and D).
Amplifier module
Model: Transistor collector open output
Power supply voltage: 24… 28 Vdc
We ship this product all over the world! Delivery is usually stock.
Amplifier module
Model: Transistor collector open output
Power supply voltage: 24… 28 Vdc
Authentication: No
Honeywell EG1033AA01 Flame detector amplifier
The number is GE 261A1812P2
The Honeywell LG/EG Flame monitoring system detects ultraviolet radiation from hydrocarbon flames and produces an output signal to indicate flame or no flame. The system has delivered more than 35 years of proven performance on GE (and GE license-holders) gas turbines.
Reviews