Electrical Ratings
Backplane Current Load: 800 mA @ 5.1 Vdc; 3 mA @ 24 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g, operational; 50 g, non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity: 5% to 95% with no condensation
All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground conductors must be at least
4mm(squared).

Categories:
Tags:
Email:jllucky33@qq.com
phone:(86)17372046300

Product content

Model: MVI56-MBP

Electrical Ratings
Backplane Current Load: 800 mA @ 5.1 Vdc; 3 mA @ 24 Vdc
Operating Temperature: 0°C to 60°C (32°F to 140°F)
Storage Temperature: -40°C to 85°C (-40°F to 185°F)
Shock: 30 g, operational; 50 g, non-operational; Vibration: 5 g from 10 Hz to 150 Hz
Relative Humidity: 5% to 95% with no condensation
All phase conductor sizes must be at least 1.3 mm(squared) and all earth ground conductors must be at least
4mm(squared).
Label Markings
ATEX
II 3 G
EEx nA IIC T6
0°C <= Ta <= 60°C

System Requirements
The MVI56-MBP module requires the following minimum hardware and software
components:
 Rockwell Automation ControlLogix™ processor, with compatible power
supply and one free slot in the rack, for the MVI56-MBP module. The module
requires 800 mA of available power.
 Rockwell Automation RSLogix 5000 programming software version 2.51 or
higher
 Rockwell Automation RSLinx communication software
 Pentium® II 450 MHz minimum. Pentium III 733 MHz (or better)
recommended
 Supported operating systems:
o Microsoft Windows 10
o Microsoft Windows 7 Professional (32-or 64-bit)
o Microsoft Windows XP Professional with Service Pack 1 or 2
o Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3
o Microsoft Windows Server 2003
 128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
 100 Mbytes of free hard disk space (or more based on application
requirements)
 256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024  768 recommended)
 ProSoft Configuration Builder, HyperTerminal or other terminal emulator
program.