Calibration requirements: P0916NG modules and end components do not require calibration. Each channel is isolated from all other channels and geoelectrics. The module can withstand a 600VAC voltage applied for one minute between any channel and ground or between a given channel and any other channel without damage.
Categories: FOXBORO
Tags: P0916NG
Email:jllucky33@qq.com
phone:(86)17372046300
Product content
P0916NG output module is connected to the field bus
Model: P0916NG
Calibration requirements: P0916NG modules and end components do not require calibration. Each channel is isolated from all other channels and geoelectrics. The module can withstand a 600VAC voltage applied for one minute between any channel and ground or between a given channel and any other channel without damage.
Communication: Communication with its associated FCM or FCP via a redundant 2Mbps module fieldbus
Inductive load: The P0916NG module output may require a protective diode or metal oxide varistor (MOV) to be connected to the inductive load.
Load current – 8 A at 20 ms per channel at 30°C (maximum) and 6.4 A at 20 ms per channel at 70°C (maximum).
On-state voltage drop: 0.2V at 2.25A (Max)
Input voltage range (redundancy)24VDC+5%, -10% power consumption (Max)
Storage condition
Temperature -40 to +85 degrees Celsius (-40 to +185 degrees Fahrenheit)
Relative humidity 5 to 95%(non-condensing)
Height -300 m to +12,000 m (-1,000 to +40,000 ft)
contaminate
P0916NG is suitable for use in G3 (harsh) environments defined by ISA standard S71.04 for exposure testing in accordance with ELA standard 364-65, Class I.
Vibration
7.5m/s2M5 Hz to 500 Hz