2024-06-27

What points should you pay attention to when choosing switching power modules?

 

What points should you pay attention to when choosing switching power modules?

GE 745 W3P5G5HIR Multilin Motor Management Relay.                         Loc4B
GE Multilin Transducer I/O Module UR 5DH 4 RTD Inputs 4 dcmA Outputs Used
NEW GE Multilin Module UR-8FH GE With 90days warranty
GE Multilin sr745 / SR745 Transformer Management Relay SR745-W2-P5-G5-HI-A-E
GE MULTILIN MF II DIGITAL FEEDER RELAY MIFIIPI5NE20HI00
[Used] GE / T60H03HCHF8FH6DM8HP6BUXXWXX / CASE, FRONT PANEL T35G03HCHF8NH6NM8NP6
GE EPM-4000 / EPM4000 PL4000R06L120 Multilin Multi-Point Submetering System
GE UR8LH UR 8LH GE multilin UR  Module
GE Multilin G60 Generator Protection System UR PLC Rack w Display Panel NO PLCS
UR-7CM UR7CM UR 7CM GE Multilin COMMS 7C 1300nm Single-Mode Module 1x New FEDEX
NEW GE MULTILIN F35 Feeder Protection System F53U04HKHF8LH6TM6EP6TUXXWXX relay

Switching power supply in the input anti-interference performance, due to the characteristics of its own circuit structure (multi-level series), the general input interference such as surge voltage is difficult to pass, in the output voltage stability of the technical

index compared with the linear power supply has a greater advantage, its output voltage stability can reach (0.5 ~ 1) %. Switching power module as a power electronic integrated device, in the selection should pay attention to the following points:

1 Selection of output current

Because the switching power supply work efficiency is high, generally can reach more than 80%, so in the selection of its output current, should accurately measure or calculate the maximum absorption current of the electrical equipment, so that the selected switching power supply has a high performance-to-price ratio, usually the output calculation formula is:

Is=KIf

Where: Is – rated output current of switching power supply;

If – the maximum absorbed current of the electrical equipment;

K – margin coefficient, generally 1.5 ~ 1.8;

2 Grounding

Switching power supply than linear power supply will produce more interference, common mode interference sensitive electrical equipment, should take grounding and shielding measures, according to ICE1000, EN61000, FCC and other EMC restrictions, switching power supply are taken EMC EMC measures, so the switching power supply should generally have EMC EMC filter. For example, Leadworth technology’s HA series switching power supply, its FG terminal is connected to the ground or to the user’s housing, in order to meet the above electromagnetic compatibility requirements.

3 Protection circuit

Switching power supply in the design must have overcurrent, overheating, short circuit and other protection functions, so in the design should be preferred with complete protection of the switching power module, and the technical parameters of its protection circuit should be matched with the working characteristics of the electrical equipment, to avoid damage to the electrical equipment or switching power supply.